Application
For simple applications, additional to smoke detectors.
Detection of smokeless combustible liquid and gas fires, as well as smoke-forming open fire involving
carbonaceous materials as contained in wood, plastics, gases, oil products etc.
Only used without source of interference as sun, halogen light, and blackbody radiation.
Can be used as an addressable, collective or conventional device.
Function
1 infrared sensor with detection algorithms.
Communication protocol |
C-NET, collective, conventional |
Operating voltage addressable / collective, conventional |
12... 33 VDC / 16... 28 VDC |
Operating current addressable, collective, conventional |
0.7 mA / 0.5 mA |
Ext. alarm indicator |
2 |
Connection terminals |
0.2… 1.5 mm2 |
Operating temperature |
-25... +70 °C |
Storage temperature |
-40... +75 °C |
Humidity |
≤95 % rel. |
Color |
white, ~RAL 9010 |
Protection category EN60529/IEC529 |
IP44 |
System compatibility collective, conventional |
CZ10, BC10, FC10, XC10, CS11, FC700A, |
System compatibilityC-NET |
FS720 |
Standards |
EN54-10, EN54-17 |
Dimensions |
135 x 135 x 77 mm |
Approvals |
VdS G204009, LPCB 126af/02 |
For simple applications, additional to smoke detectors. 1 infrared sensor with detection algorithms.
Base for FDF241-9 Flame Detector and FDF221-9 detector
Detects smokeless liquid and gas fires as well as any combustion of carbonaceous materials using 3 infrared sensors with ASAtechnologyâ„¢.
The mounting bracket for volumetric surveillance, fixed the detector in the right angle.
MWV1 Ball and socket joint for the flame detector for the orientation to a defined object.
DFZ1190 Rain hood for the flame detector for outdoor applications.